IEEE C37.27-2015 pdf free.IEEE Guide for Low-Voltage AC (635 V and below) Power Circuit Breakers Applied with Separately- Mounted Current-Limiting Fuses.
current-limiting peak let-hrough or cutof0 characteristic curve: A curve showing the relationship between the maximum peak currcent pased by a device and the correlated rms available curcent magnitude under specified vollage and circuit impedance conditions.
curren-limiting. fuse: A fuse that, within a spedfied overcurrent range. limits the clearing time a rated voltage to an interval equal to or less than the first major or symmetrical current loop duration;and limits the peak current to a value less than the availble peak current.
NOTE-The values specified in standards for the threshold ratio peak ltthrough current, and charateristics are used as the measures of current-limiting abiliy.
current-limiting range (of a current-limiting fuse: That specifed range of currents between the threshold current and the rated interrupting current within which current limitation occurs.
fuse: An overcurrent protective device with a circuit-opening fusible part that is heated and severed by the passage of overcurrent throughit.
NOTE-A fuse comprises all the parts that form且unit capable of performing the prescribed functions. It may or may not be the complete device necessary to connect i into an tlectric cirouit.low-voltage fused power circuit breaker: An assembly of an ac low-voltage power cirouit breaker with either integrally mounted or nonintegrally mounted current-imiting fuses that together function as a coordinated protective device.
low-voltage integrally fused power circuit breaker: An assembly of an ac low-voltage power circuit breaker with current-limiting fuses integrally mounted to the circuit breaker and that function together as a coordinated protective device.
low-voltage nonintegrally fused power circuit breaker: An assembly of an ac low-voltage power circuit breaker and nonintegrally mounted current-limiting fuses that together function as a coordinated protective device.
low-voltage power circuit breaker applied with separately mounted current-limiting fuses: Any combination of a low-voltage power circuit breaker and current-limiting fuses other than integrally and nonintegrally fused ac low-voltage power circuit breakers as defined by IEEE Std C37.13.
peak let-through cutoff current (of a current-limiting fuse): The highest instantaneous current passed by the fuse during the interruption of the circuit.
total clearing time of a fuse: The time elapsing from the beginning of a specified overcurrent to the final circuit interruption, at rated maximum voltage.IEEE C37.27 pdf free download.