Home>IEEE standards>IEEE 1564-2014 pdf free

IEEE 1564-2014 pdf free

IEEE 1564-2014 pdf free.IEEE Guide for Voltage Sag Indices.
The following referenced documents arc indispensable for the application of this document (i.e.. they must be undcrstood and used, so cach referenced document is cited in tcxt and its relationship to this document is explained). For dated references, only the edition cited applies. For undated references, the latest edition of the rekrenced document (including any amendments or corrigenda) applies.
IEC 61000.2.8, Electromagnetic compatibility (EMC)—Part 2.8: Environment—Voltage dips and short interruptions on public electric power supply systems with statistical measurement results.
IEC 61000-4-11, Electromagnetic compatibility (EMC) Part 4-Il: Testing and measurement techniques——Voltage dips. short interruptions and voltage variations immunity tests.
IEC 61000-4-30, Electromagnetic compatibility EMC) – Part 4-30: Testing and measurement techniques— Power quality measurement methods.
IEEE SW 1159, IEEE Recommended Practice for Monitoring Electric Power Quality.2’3 IEEE SW 1366 . IEEE Guide for Electric Power Distribution Reliability Indices.
For the purposes of this document, the Ibllowing terms and definitions apply. The IEEE Standards Dictionary Online should be consulted for terms not defined in this clause,4
characteristic oltage (of a voltage sagj: A single-event characteristic that combines the voltages in the three phases providing one single value corresponding to the sliding-window root-mean-square Crms) voltage as defined for single-phase recordings. The characteristic voltage is the lowest of the three per-unit phase-to-phase rms voltages, and the three per-Unit phase-to-ground rms voltages after removing the zero- sequence component.
declared soltage: The nominal voltage or a value of a voltage different from the nominal voltage obtained by agreement between the electricity supplier and a consumer.
NOTE—See IEC 6lfl00-4-30.
depth (of a voltage sag): The difference between the reference voltage (either or V5) and the residual voltage. It is generally expressed in percentage of the reference voltage.
NOTE—See I EC 61000-4-30.
duration lola sultagr sag: The length of the interval between the time when the root-mean-square Irms) voltage drops below the sag threshold and the time it subsequently rises ahose the sag threshold.IEEE 1564 pdf download.

Related PowerPoint Templates